
email me - warrens@ns.sympatico.ca

The house is heated by oil fired hot water baseboards. There were originally had three heating zones. Three bedrooms shared one zone and a common thermostat. Invariably one bedroom was much colder than the others and attempts to regulate temperature by adjusting the vents on the heaters and relocating the control thermostat were only moderately successful. In order to provide best temperature control and maximum comfort, I decided to split the bedroom zone. Two thermostats were added, and plastic heating pipes put in place to direct heated water to the proper zones. The furnace needed the manifolds expanded and zone control valves put in place and wired. Each bedroom now has an independant thermostat.
The entire basement (except garage) is on another zone. I will move an unfinished basement room to its own thermostat in the future. There is an added output on the manifold to accomodate this. The thermostat wire is installed and ready for connection.
The entire heating system needed to be bled to eliminate air bubbles. Small bubbles remaining are automatically bled as the pump circulates water.
All thermostats are programmable types. Temperature is automatically reduced overnight.
Click thumbnails to enlarge
Start of project. Three heating zones.
Original 3 port return manifold.
Assembled 3 port expansion manifold.
3 port return expansion manifold mounted.
3 port return expansion manifold with two new lines attached.
Assembled 3 port source manifold.
3 port source expansion manifold mounted.
3 port source expansion manifold mounted and wired.
Rear view of 3 port source expansion manifold.
Completed project. Two zones have been added and a third port is available.
Orange pipes are newly added. All lines are held to beams with copper straps.
Typical splice used for splitting heating zones. Four splices were required to split the single bedroom zone into three.
Cold water enters the furnace from the 1/2 inch pipe, through the ball valve (turned off), one way check valve, and pressure regulator. I leave the ball valve turned off. If there were a leak in the system, it would be limited to the water in the furnace. With the valve open, water leaking would be immediately replaced and the flood could be disastrous. I occasionally open the valve to ensure the system is operating at proper pressure, but have never noticed a problem.
Hot water exits the furnace and flows through a ball valve, past the drain valve, and circulating pump. The expansion tank is green (tank has been relocated to allow easier access on side of furnace, compare to other pictures), above is the automatic air purge screw at the very top. From here the water will flow through the source manifold, through the zone valves, and warm the room. Cooled water returns through the return manifold to the base of the furnace where it is heated and recirculated.
To bleed air from the system, turn off the furnace AC power switch to prevent the furnace from running constantly. Attach a hose to the drain valve and turn off the ball valve beneath the drain. Open the ball valve to allow cold water to enter the furnace. Open the drain valve and push the lever at bottom of the zone valve to allow water to flow. Watch for bubbles at the end of the hose. When there are no more bubbles close the zone valve and move to the next one.
After all zones have been purged, close the drain valve and cold water intake valve. Now open the ball valve beneath the drain and the system should be ready to go. Any small bubbles remaining will be automatically purged. Make sure the black screw above the expansion tank is loose to allow air to escape.
I place shrink plastic on windows to reduce draft and heat loss.
Becket Heat Manager claims to save 10% on fuel consumption. After reading the
product specs,
I adjusted the thermostats on the furnace to operate between 155F and 175F.
If that's all the device does I can do it more inexpensively and easier.
(Spec sheet originally downloaded from http://www.patriot-supply.com/files/beckett_7512_data_sheet.pdf)
Here is a picture of the thermostat and the new settings.
Click for a larger image.
From Nova Scotia Power -
Top 10 hot tips to stay warm & reduce energy costs
This Spring, after hearing the furnace cycle several times during the night to keep its internal tank heated I decided to do something about this apparent waste of energy. In summer the sides of the furnace are noticeably warm, radiating heat into the basement. There is no requirement for hot water while everyone is asleep. I installed an electronic timer in series with the main shut off switch to automatically turn off the furnace overnight and during the day while everyone is at work. The furnace is turned on in the morning when we are getting out of bed and preparing for the day, as well as when we get home for the evening. Installation is little more complicated than putting in a light switch, followed by simple programming of the timer. I expect it to pay for itself over the course of the summer.
I bought the timer for $30 at Canadian Tire, item number is 52-9907-6. It is made by UPM, model
ETW 350.
Conserving on your Heating Bill, from Yahoo!
Tips For Homeowners to Conserve on Heating Bills